Wednesday, May 20, 2009

DCAP 3000 | PLTM Mobuya General Protection

PLTM Mobuya, using DCAP-3000 Series Ptrotection & Control Devices. Designed to be used for measurement, control and protection of power equipment in medium and high voltage networks. State of the art digital technology integrates all the secondary functions into a single unit, installed directly on switchgear and in switch-bay beside switching object. Connecting all these device in a station via RS485 communication interface with shielded twisted wire to construct an integrated automation system.

For Protection, PLTM Mobuya Using :
DCAP-3001, transformer feeder protection & control device, applicable to transformer feeder and station-used transformer with a circuit breaker
DCAP-3040, two-winding differential protection device. Suitable for power transformer, generator-transformer blocks and power reactors, adopts 2nd harmonic/waveform symmetry restraint for inrush current (optional) and percentage restraint principle.
DCAP-3080, generator protection & control device, applicable to medium-sized generators of 200 MW or lower. Protection including overcurrent protection, undervoltage protection, overvoltage protection, zero sequence overvoltage protection, negative sequence overcurrent protection, reverse power protection, under and over frequency protection.
DCAP-3083, designed for one-point or two-point earth-fault protection of a synchronous machine rotor. The device is applicable to all sorts of capacity of synchronous machines.

PLTM Mobuya Single Line Diagram

PLTM Mobuya Turbine and Generator


PLTM Mobuya Turbines Unit 1 to 3, manufacturing by Zhejiang Jinlun Electromechanical Co. Ltd. on November 2005 Type : Franciss Horizontal - HLD46-WJ-60 Output : 690 – 1758 kW Head : 50 – 100 m Speed : 750 – 1000 rpm.


PLTM Mobuya Synchronous Generator Unit 1 to 3, manufacturing by Zhejiang Linhai Electric Machinery Co. Ltd, on November 2005 Type : SFW-J1000-6/1180 Power : 1000 kW Voltage : 6300 V Current 114.6 A Connection : Y Fields Voltage : 40.3 V Fields Current : 288 A Excitation : Thyristor Speed : 1000 rpm Runaway Speed : 1900 rpm


Sistim Kaskade PLTA Sungai Poigar

Sunday, May 17, 2009

PLTM Mobuya - Sulawesi Utara

PLTM atau Pusat Listrik Tenaga Minihidro merupakan pembangkit tenaga listrik yang menggunakan sumber energi setempat dan juga merupakan sumber energi terbarukan serta ramah lingkungan PLTM Mobuya yang memanfaatkan potensi tenaga air sungai Poigar didesa Mobuya., kecamatan Passi Kabupaten Bolaang Mongondow, merupakan salah satu potensi tenga air untuk pembangkit tenaga listrik minihidro yang layak secara ekonomi dan finansial untuk diuasahan oleh Badan Usaha Kecil dan Menengah mengikuti ketentuan dalam Kepmen No. 1122/30/MEN/2002 tentang Pedoman Pengusahaan Pembangkitan Tenaga Listrik Skala Kecil.

PLTM Mobuya dengan kapasitas terpasang 3 x 1000 kW dapat menghasilkan energi listrik sebesar 21.000.000 kWh rata-rata pertahun akan memenuhi kebutuhan tenaga listrik untuk sistim Kotamobagu dan sekitarnya. Daya listrik yang dihasilkan akan disalurkan melalui sistim jaringan tegangan menengah 20 kV PT PLN( Persero ) Wilayah Sulawesi Utara, Sulawesi Tengah dan Gorontalo.

Deskripsi PLTM Mobuya
Debit (Q) : 3 x 1,67 m3/detik (5 m3/det)
Tinggi Jatuh (h) : 71,0 meter
Kapasitas Terpasang : 3 x 1.000 kW
Energi Tahunan : 21.024.000 kWh
Your Ad Here